XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.01.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Rest
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.30 V
Current 4.08 A
Power 406 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 3,072 Wh
Output
Voltage 87.01 V
Power 286 W
Apparent Power 345.42 VA
Frequency 60.05 Hz
Percent Load 26.40 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 3.97 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 91
Time Since Last Standby Event 65d 8h:43m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 1,628 min
Standby Events Since Reset 33
Time in Standby Since Reset 1,206 min
Time Since Reset 1,082 day(s)
Total Run Time 1,082 day(s)
Transformer Run Time 1,082 day(s)
Total Downtime 0d 5h:22m
Oil Cap Lifespan Consumed 38.2 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 27 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 